Eaton 9130 3000 VA Rackmount

General Characteristics
Topology Online, double-conversion
Configuration Rackmount
Part Number 103006463-6591
Color Black
Rating (VA/Watts) 3000/2700
Diagnostics Full system self-test
Efficiency 94% in high-efficiency mode; 90% in online mode
UPS Bypass Automatic bypass
Dimensions (H x W x D, mm) 86.5 x 438 x 600
Weight (kg) 29.5
Rail Kit Included Yes
Remote Emergency Power off (REPO) Emergency shutdown control through the REPO port
Electrical Input
Connection (1) С20
Input Cord Schuko 10A to IEC 320-10A
Input Voltage Range 180-276 Vac (with load PF of 0.7)
Nominal Voltage 220 - 240 V
Frequency 50/60 Hz
Frequency Range 45–65 Hz
Nominal Current 13.0A @230V
Breaker Ratings 16A
Electrical Output
Output Receptacles (8) C13, (1) C19
On Utility Voltage Regulation ±3% of nominal
Frequency Regulation ±3% Hz online
Load Crest Factor 3:1
Battery
Battery Description VRLA 12V/9 Ah (internal and External)
Battery Type Replaceable maintenance free sealed lead acid
Battery Replacement Hot-swappable internal batteries
Start On Battery Allows start of UPS without utility input
Communications
User Interface Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish
LEDs Four status-indicating LEDs
Communication Ports RS-232 and USB HID port as standard
Relay Output Common alarm standard
Communications Slot Optional communication slots (BD Slot)
Communications Card Slots Optional SNMP/Web card for monitoring in SNMP-based networks, monitoring through Web browser interface. Relay card for integration to industrial environment and BMS, remote shutdown for IBM AS/400 systems
Environmental & Standards
Heat Dissipation (BTU) Line: 1257, Bat: 1755
Audible Noise <44 dB
Operating Temperature 0°C — +40°C
Performance - Safety - EMC CE (per IEC/EN62040-2: Emissions, Category C1; Immunity, Category C2), GS
Storage Temperature -20°C to +40°C with batteries and -25°C to +55°C without batteries
Relative Humidity 5–90% non-condensing